Mains Connection | Input voltage | 1ph 220-240 V; 3ph 380-460 V |
Input frequency | 50-60 Hz (+/- 2%) |
Displacement power factor (cosphi) near unity | > 0.98 |
Motor controls | Control methods | V/F and SVC (Sensorless Vector Control) |
Control type | PWM (pulse width modulation) |
Frequency Setting Resolution | Digital Reference: 0.01 Hz |
Frequency Accuracy | Digital: 0.01 % of Max. Output Frequency |
V/F Control Curve | Adjustable V/F curve |
Maximum Output Frequency | 1ph 220-240 V models: 300 Hz; 3ph 380- 460VAC models: 300 Hz |
Overload Capacity | 110% of VFD rated current for 1 minute during every 5 minutes of operation |
Protection | Operation Method | Keypad / Terminals / RS-485 Modbus Communication / Bluetooth Mobile App control |
Analog Input | 4 Analog Inputs (2x 0- 10VDC) (2x 4- 20mA) |
By Digital Inputs | Start Signal | Forward, Reverse |
Stop Signal | Motor ramp down |
Digital Input | 4 programmable digital inputs (Normally Open / Normally Closed), motor run, motor stop |
Fault Reset | Resets VFD faults via keypad, digital input or communication. Some critical faults can only be reset by cycling the VFD power. |
Outputs | 2x Multi-Function Outputs | 2 programmable digital outputs (NO, NC), motor run signal, alarm signal |
RS 485 Serial Port | Output Frequency, Output Current, Output Voltage, Output kW, DC Link Voltage |
General Operation Functions | Frequency Limit, Jump Frequencies, 2nd ACC/DEC, Auto Restart, Auto-Tuning, PID w/sleep, Temperature Foldback, Run Delay, Minimum Run Timer, PM Motor Control and Auto-Tuning |
Pump Operation Functions/Protections | Sleep Mode, Pipe Fill, PID, Overpressure, Dry Run (Underload), HLD (High Load), Broken Pipe, No-Flow Protection |
VFD Fault Trips | Over Voltage, Low Voltage, Over Current, Overload, Short Circuit, Ground Fault, VFD Overheat, Input Phase Loss, Signal Loss, Hardware Fault, etc. |
Motor Overload | Adjustable electronic motor overload protection |
Motor temperature | 3-wire PT100 motor temperature protection (on request) |
Overcurrent | 220-240 VAC variable torque: at 110% of VFD rated current 380-460 VAC variable torque: at 110% of VFD rated current |
Overvoltage | 380-460 VAC models: at 820VDC DC bus voltage |
Overtemperature | Built-in IGBT and capacitor bank temperature sensors |
VFD Alarm | Stall Prevention at ACC and DEC, Overload, Thermal Sensor Fault, Capacitors High Temperature, Signal Loss, Overpressure, Underload, High Load, etc. |
Keypad Display | Operation Information | Output Frequency, Output Current, Output Voltage, Frequency Reference, Operating Speed, DC Voltage, kWattmeter, Run-time, Last Trip Time, Pressure, etc. |
Fault | Provides 6 fault records and logs 30 faults |
Environ- ment | Operating Temperature | -10 °C ~ 40 °C (14 °F ~ 104 °F) |
Storage temperature | -10 °C ~ 60 °C (14 °F ~ 140 °F) |
Ambient Humidity | up to 95 % RH. (non-condensing) |
Altitude | Normal up to (1000 m), -1% derating every 100 m |
Vibration and Impact | Complies with EN 60068-2-6:2008 and EN60068-2-27:2009 and EN60068-2-64:2008 |
Enclosure Ratings | IP66 |
Max. Input efficiency (>=X%) | Drive model | DrivE-Tech MINI | DrivE-Tech COMPACT |
Input voltage | 220-240 AC | 95 | 95 |
380-460 VAC | 96 | 97 |
CE Low Voltage | EN6100-5-1 |
CE EMC | EN61800-3, EN61000-3-12, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-6-2, IEC61000-6-4 |
Other | C-Tick, ROHS |